Generator noise at a site boundary: a worked example
How much noise might a generator contribute at a boundary 50 m or 100 m away? This synthetic example documents the source spectrum, geometry and output of the current draft engine. It is a reproducible software example, not a measured generator specification or a compliance assessment.
Start a free calculationThe model inputs
One omnidirectional point source is at (0, 0), height 1.5 m. Receivers are at (50, 0) and (100, 0), both at 1.5 m. Coordinates are metres in a local plane; the receivers are not attached to a reflecting facade. The ground factor is G = 0 throughout. There are no screens or buildings, and reflections are disabled.
The source operates throughout the 16-hour day period used by the browser when the project has no assessment framework. Temperature is 15 °C and relative humidity is 70%, the current fixed browser defaults. The result shown here is the favourable-condition level. These defaults are example settings, not measured site meteorology.
| Octave band, Hz | Whole-source sound power Lw, dB |
|---|---|
| 63 | 90 |
| 125 | 94 |
| 250 | 96 |
| 500 | 93 |
| 1000 | 89 |
| 2000 | 85 |
| 4000 | 80 |
| 8000 | 72 |
Output of the draft propagation engine
Calculated on 25 October 2026 with core version 0.1.0, method cnossos-eu:2021. Unrounded favourable-condition levels are 52.44145135 and 46.81153507 dBA. This is the condition currently displayed by a browser project without an assessment framework. It is not a long-term average over a chosen meteorological probability.
The difference is 5.63 dB. It need not be exactly the 6.02 dB of geometrical spreading alone: the propagation model also includes ground and atmospheric terms. No background noise or assessment penalties have been added to the values in the table.
| Receiver | Horizontal distance, m | Favourable-condition level, dBA |
|---|---|---|
| R50 | 50 | 52.4 |
| R100 | 100 | 46.8 |
Reproduce the example
- Create a project without an assessment framework for this control example, using the default 16-hour day period. Enter the spectrum above as sound power, not sound pressure. The 31.5 Hz band is not used by the current eight-band method.
- Set source and receiver heights to 1.5 m and verify actual source-to-receiver distances of 50 m and 100 m. Core coordinates are local metres; geographic map placement must preserve the same geometry.
- Use the default hard ground (no added surface zones), no obstacles or reflections, no background, and full day operation. The current browser adapter fixes temperature at 15 °C and relative humidity at 70%; check these recorded settings in the report.
- Compare the favourable-condition levels before adding a framework criterion. The current browser does not provide a favourable-probability control or JSON import for these files. The JSON is a complete core reproduction record; a different framework, propagation condition or geometry can change the displayed result.
Use the example as a setup check
For an actual generator, obtain manufacturer or measured octave-band data for the correct operating load, enclosure and exhaust configuration. Strongly tonal or impulsive noise needs specialist consideration beyond this example. The equipment name alone does not determine sound power.
The draft method has not been independently validated. Atmospheric absorption verification and other method limitations remain open. Treat these outputs as a reproducibility reference for this software version; the decimal places are not an accuracy claim.
Early preview. Screening-level estimates do not replace an assessment by a qualified specialist. The calculation is free and you can start without an account.